CVD Equipment Corporation > Stainless Design Concepts Our Companies:

sdc logo
enabling tomorrow's technologies™

AtomVault™ Gas Cylinder Storage Cabinet

Download Atomvault Brochure pdf

Specialty Gas and Chemical Delivery and Storage Systems are engineered to meet tomorrow’s standards for Ultrahigh Purity, safe handling of your hazardous gases and liquids. Through the SDC brand name and private label equipment in stallations, SDC has emerged as a leader in safe, UHP, low cost specialty gas and chemical delivery equipment.

Standard Configurations:

  • Delivery and Storage Systems
    Eleven (11)-gauge cold rolled
    steel body
  • High quality, fully seam-welded
    construction
  • Low profile ¼" diamond-plate
    hard-deck
  • Large view, gasketed, fire rated,wire-reinforced safety glass viewing window
  • Protective Lexan® shield behind
    access door
  • Self-closing, self-latching gasketed, triple-hinge doors.
  • Lockable safety latches
  • Lockable access door (>150 f/m face velocity while open at recommended exhaust rates)
  • Thirty-one (31) gpm bee’s waxcoated sprinkler heads rated for 165 °F
  • Laser cut intake grille
  • Unistrut® compatible interior mounting rails
  • Seismic tie-down clearance holes for 5/8" bolts
  • Cylinder clamps with tensionstraps
  • Light gray, textured, ruggedized polyurethane finish
  • Plumbing backplanes

Optional Features:

  • Adjustable cylinder shelves
  • Air intake filters
  • Plumbing backplane
  • Custom cabinet colors
  • Custom laser cut intake grille
  • Custom labeling and logos
  • Lecture bottle stands
  • Chains in lieu of self-tightening straps
  • Exhaust pressure switch (monitored by others)

Codes and Standards Referenced:

  • OSHA® 29 CFR 1910, subparts S and H
  • NFPA® 497 Classifications of Hazardous Locations for Electrical Installations in Chemical Process Areas
  • SEMI® S2 Safety Guidelines for Semiconductor Manufacturing Equipment
  • SEMI® S8-95 Safety Guidelines for Ergonomics/Human Factors Engineering of Semiconductor Manufacturing Equipment
  • SEMI® S6-93 Safety Guidelines for Ventilation
EXHAUST SPECIFICATIONS/REQUIREMENTS
Cabinet Model Exhaust Configuration * Min. Exhaust Flow
1-Cylinder One 6" OD stub
150 CFM
2-Cylinder One 6" OD stub 300 CFM
3-Cylinder Two 6" OD stubs 450 CFM
4-Cylinder Two 6" OD stubs 600 CFM
1-Dewar One 8" OD stubs 500 SCFM
2-Dewar Two 8" OD stubs 1000 SCFM

*Depending on the specific gas and the combined volume, this flow may be higher.