FlexGas™ Cylinder Gas Cabinet
The FlexGas™ Cylinder Gas Cabinet is designed to cover a wide range of cylinder gas delivery applications. In its simplest form, the FlexGas™ Gas Cabinet houses 1, 2, or 3, gases, and includes a high purity, manual gas panel for each gas. Modular FlexGas™ Panels are available in 1, 2, 3, 4, 5, and 6-Valve designs and may be tailored to the specific gas and application.
With the addition of the optional FlexPowr™ Controller, the FlexGas™ Cabinet can support a myriad of automated features such as auto-switchover capability, excess flow sensors, low cylinder pressure alarms, high delivery pressure alarms, gas leak sensors, scales and more. The FlexPowr™ Controller also supports user-settable alarm inputs and user-settable alarm outputs. The EMO slam button and exhaust pressure sensor are standard with the FlexPowr™ controller option.
FlexPowr™ Control Features
- Automatic shutdown of process gas panels
- Up to 10 user-definable alarms
- Up to 2 user-definable outputs
- Audible/visible alarm indication
- EMO button
- Multilevel password protectio
- LOW cylinder pressure switch
- HI or LOW delivery pressure switch
- Integrated gas leak detection
- Integrated UVIR sensor
- Excess flow sensor
Process Panel Features
- 1, 2, 3, 4, 5, and 6-valve designs
- UHP construction: orbitally welded/VCR® 316L SS or VIM/VAR
- UHP grade regulator (non-tied diaphragm standard)
- UHP grade diaphragm valves (10 Ra standard)
- Dual stage regulators
- Outlet filters (0.003 um)
- DISS cylinder fittings
- Pressure relief
Standard Configurations
- 1-cyl, [1-process]
- 2-cyl, [1-process, 1-purge]
- 2-cyl, [2-process]
- 3-cyl, [3-process]
- 3-cyl, [2-process, 1-purge]
* Optional Purge SideCar
Dimensions
- 1-cyl: 18"W x 72"H x 19"D
- 2-cyl: 24"W x 72"H x 19"D
- 3-cyl: 36"W x 72"H x 19"D
Options
- Adjustable cylinder shelves
- Vesta heat control system
- Outlet splitters
- Cylinder scales
- Coax jacket monitor
- Restrictive flow orifices
Codes and Standards
- ASME Section IX
- CGA®
- CE®
- Semi S2®
- NFPA®
- UL®
Exhaust Specifications & Requirements
1Pneumatic Supply | adjustable to 90 psig | 1 slm max. |
2Process Purge | adjustable to 85 psig | 30 slm max. |
3Vacuum Drive | adjustable to 60 psig | 70 slm max. |
4Process Vent | >1.0" WC | 100 slm |
1Power | 115V / 3A | N/A |
Sprinkler | 30 psig | 31 gpm |
5Exhaust | >0.15" WC | 300 scfm (2-cyl) |
2Required with 4-Valve, 6-Valve gas panel configurations
3Required with 6-Valve gas panel configurations
4Required with 3, 4, 6 -Valve gas panel configurations